Categories



The complete product assortment of the GSG Geologie-Service GmbH

According to your requirements we are arranging together with
you the optimum system for your individual application
Please describe us your requirements, our team will contact you as soon as possible.

You are reaching us by e-mail: 
mail@geologie-service.de
or by:
Phone: +49 (0)931/30 40 8-0
Fax: +49 (0)931/99105 90



GIR 2002 - Details

Home --> Devices for Switch Panels / Industry --> Controller - Measuring and Regulating Devices


Universal measuring and controlling device GIR 2002 and GIR 2002 PID - easy operating, high precision, favourable price - Greisinger electronic

Universal Measuring and Regulating Device

easy to use - high precision - favourable price

Highlights:
 
  • universal input for standardized signals, frequency, Pt 100, Pt 1000, thermocouples

  • 2 relay switching outputs

  • 1 analog output 0(4) - 20mA or 0 to 10V) (optional)

  • 5 programmable switching functions

  • electrical isolated power supply for transitter (24V / 22mA)

  • serial interface, bus operation

In addition at GIR 2002 PID:
  • P, I, PI, PD or PID control mode
  • motorised valve control
  • continuous regulating output (optional)
GIR 2002     On/Off - control mode

                               

GIR2002

 

GIR 2002 PID   with PID - control mode 

 

                                                                     

 

 
General information
 
The universal controller GIR 2002 is the ideal device for simple controlling systems (on/off switching, relay outputs, ...),
because of its compact construction and its high ease of use.

The GIR 2002 PID (basic version) supplies one control output for a 2-point regulation with the control modes  P, I, PI, PD or PID
as well as a second control output for on/off switching mode.
The device can also be configured as a 3-point motorized valve controller as well as optionally as controller with continuous output.

Due to the universal input and the various switching functions the controller can optimally be adapted to the requirements of your system.
The structured menu navigation allows an uncomplicated handling and a fast adjustment of the parameters.

A LED switching position display gives information to the user about the current status of the switching outputs.

The voluminous automatic self-test and diagnostic system increases the operational safety and reports system errors
by means of conclusive error codes.
The parameters are automatically memorized so that all data will be maintained even in case of a power blackout.

Among others most of the Greisinger transmitters, rpm sensors and flow rate sensors can be connected directly to the integrated transmitter power supply (24VDC/22mA) of the controller.

If the device is used as a thermocouple or resistance thermometer, the measuring value can alternatively be indicated in °C or °F.
In addition the values masured can be adjusted e.g. to the resistivity of the wires by means of an offfset correction
The current and voltage inputs can be arbitrarily scaled within the range of -1.999 to +9.999.

The GIR 2002 has got a serial, bus-compatible interface, by which a comfortable programming of the parameters as well as recording
of measured values is possible. With the optionally available Windows library EASYBUS.dll up to 240 devices can be integrated into own programs (i.e. LabView).

 

Specification
Outputs: Please note: Not all options are available for both device types and not all options
can be combined one with each other. Please have therefore a look at the output options diagram below.
Output 1: potential-free relay output (standard)
normally-open contact, switching power: 5A (ohmic load), 250VAC
optional Output 1: - HLR1: control output for semiconductor relay (6VDC/15mA)
- AAG..1: freely scaleable analog output 0(4)-20mA or 0-10V
- ST..1: continuous output 0(4)-20mA or 0-10V
Output 2: potential-free relay output (standard)
change-over contact, switching performance: 10A (ohmic load), 250 VAC
optional Output 2: HLR2: control output for semiconductor relay (6 VDC/15mA)
Output 3: (not available at standard device type)
optional Output3: - AAG..3:freely scaleable analog output 0(4)-20mA or 0-10V
- ST..3: continuous output 0(4)-20mA or 0-10V
- REL3: potential-free relay switching contact (change over contact)
           switching performance: 1 A / 40 V AC resp. 30 V DC
- HLR3_ control output for external semiconductor relay (14 V DC / 15mA)
- NPN3: electric-isolated NPN switching contact (max. 1A / 30 V DC)
switching functions: 5 or 6, selectable
(e.g. 2-point controller, 3-point controller,...)
switching points, hysteresis: freely adjustable
response time: <25 msec.
<0.5 sec.

at standardized signal
at temperature and frequency
display:

approx.  13mm high, 4-digit red LED-display

Min-/Max-value memory:

the max- and min value will be memorized

interface:

serial interface, electrical isolated, EASYBUS compatible

power supply for sensor: 24 VDC +5%, 22mA (for DC-supply 18 VDC)
miscellaneous: permanent self-diagnosis, digital filter function,
measuring range boundary (limit)
voltage supply:

230 VAC, 50/60 Hz (standard)
optionally other voltage supplies are possible

power consumption:

approx. 6 VA

operating conditions:

-20°C to +50°C, 0 to 80% RH (non-condensing)

housing:

standard rack type housing 48x96mm (front frame)
installation depth: approx. 115mm (screw-type/plug-in terminals incl.)

panel mounting:

with fixing clamps
panel cutout: 43.0+0.5 x 90.5+0.5 mm (HxW)

electrical connection:

via screw-type/plug-in terminals
wire diameters from 0.142 to 1.5 mm2.

protection class:

front side IP54, with optional sealing IP 65

electromagnetic immunity (EMC):

EN 61326 (appendix A, class B)

 

measuring input measuring / display ranges accuracy (at nominal
temperature)
measuring rate
thermocouples:      
FeCu-Ni type J IEC 584 -70.0°C to +300.0°C or -170°C to +950°C <0,3% FS +1digit* approx. 4 meas. / sec.
NiCr-Ni type K IEC 584 -70.0°C to 250.0°C or -270°C to+1.372°C
NiCr-Si-NiSi type N IEC 584 -100.0°C to +300.0°C or -270°C to +1-350°C
Pt10Rh-Pt typr S IEC 584     -50°C to +1.750°C
Cu-CuNi type T IEC 584 -70°C to +200°C or -270°C to +400°C
resistance thermometers:      
Pt100 3 wires DIN EN 60751 -50.0°C to +200.0°C or -200°C to +850°C <0,3% FS +1 digit* approx. 4 meas. / sec.
Pt1000 2 wires DIN EN 60751     -200°C to +850°C
action signals / standardized signals:      
0 to 1V, 0 to 2V, 0 to 10V -1999 to +9999 digit, scale freely adiustable <0,2% FS +1 digit*
<0,2% FS +1 digit*
<0,3% FS +1 digit*
approx. 100 meas. / sec. 
0 to 20mA, 4 to 20mA
0 to 50mV
frequency:      
TTL-Signal 0.000 Hz to 10 kHz, scale freely adjustable <0,1% FS +1digit* approx. 100 meas. / sec. 
switching contact NPN 0.000 Hz to  3 kHz, scale freely adjustable
switching contact PNP 0.000 Hz to 1 kHz, scale freely adjustable
rotational speed: 0.000 to 9.999 U/Min. selectable prescaler: 1to1000,
pulse frequency: max. 600.000 Imp./min. at TTL
flow: 0 to 9999 l/s., 0 to 9999 l/min. or 0 to 9.999 l/h  
count up / down
(TTL-signal,
switching contact (NPN, PNP))
 
0 to 9999 or 0 to 999999 (with prescaler)
selectable prescaler: 1 to 1,000,
pulse frequency: 10.000 pulses/sec.max at TTL
<0,1% FS +1digit* approx.. 100 meas. / sec. 
serial interface: displaying and controlling from values coming via serial interface
*= accuracy of reference junction +1°C
Options:
Output surview GIR 2002 GIR 2002 PID
  out 1 out 2 out 3 out 1 out 2 out 3
Standard type: normally
open contact
change-over
contact
- normally
open contact
change-over
contact
-
available output options: against surcharges
HLR1: output 1 = control output for external SSR x     x    
HLR2: output 2 = control output for external SSR   x     x  
REL3: output 3 = relay (change-over contact)     x2     x2
HLR3: output 3 = semiconductor relay  connection     x2     x2
NPN3: output 3 = NPN switching output     x1     x1
AAG020/1: output 1 = analog output 0(4)-20mA x1   out3 not
possible
     
AAG010/1: output 1 = analog output  0-10V x1   out3 not
possible
     
AAG020/3: output 3 = analog output 0(4)-20mA     x1     x1 
AAG010/3: output 3 = analog output 0-10V     x1     x1 
STA1: output 1 = continuous output  0(4)-20mA       x1   out3 not
possible
STV1: output 1 =  continuous output 0-10V       x1   out3 not
possible
STV3: output 3 =  continuous output 0(4)-20mA           x1
STV3: output 3 =  continuous output 0-10V           x1
1 At continuous/analog output or NPN switching output with option power supply = 12 V DC or 24 V DC additional surcharge!
2 at output REL3 or HLR3 with option power supply = 12 V C aditional surcharge!



Universal measuring and regulating device - easy operability - high accuracy - economic price, basic price

temperature controller, pressure control, tachometer, flow meter...

Follower of GIR 1002 Pt100 and GIR 1002 NS

Please order the following options separately:


Please order the following accessories separately:




= data sheet as *.pdf

= instruction manual as *.pdf

deutsche Beschreibung

Price of the basic article, German V.A.T. incl : EUR 176.70


The net price of the basic article  GIR 2002 is:  EUR 148.49 