GITT 01 - Details

Home --> Devices for Switch Panels / Industry --> Measuring Transducer --> Transmitter for Universal Use


Programmable, electrically isolated Universal-Transmitter


- universally programmable for 
     - resistance thermometer
     - Thermocouples
     - resistance sensor
     - voltage sensor

- output linear to temperature

- Analog output : 4 ... 20mA,
                             2-wire technology

- electrically isolated

- high accuracy for the entire ambient 
   temperature range (-40... 85C)

- available with, EX-protection
          ATEX II 1 G EEx ia IIC T4 / T5 / T6

- error messages in case of sensor damage
   or short-circuit, settings acc. to  
   NAMUR NE 43

- can be configured in a few seconds via PC
   - configuration can be carried out during
     measuring

- CE-rating

  

 

GITT01*

GITT01 - EX

* Transmitter can either be programmed by customer or by our works - please specify type upon order
        (e.G.. GITT01, NiCr-Ni (Type K), 4 ... 20 mA = 0 - 300 C)

 

Accessories (against upcharge):

Snap-on mounting: (rail adapter for snap-on to top-hat rail)

Programming tool for GITT01, consisting of:    - configuration-software (3,5"-disk, multilingual, Online help 
                                                                           - Connection cable, RS 232-C (approx. 1m long, 9-pin Dsub-plug)
                                                                           - operating manual

Specification:

Input signal: universally programmed to
       

Resistance thermometer: max. meas. range min. meas. span
Pt 100 acc. to IEC 751 -200 ... +850 C 10 K
Pt 500 acc. to IEC 751 -200 ... +250 C 10 K
Pt 1000 acc. to IEC 751 -200 ... +250 C 10 K
Ni 100 acc. to DIN43760 - 60 ... +180 C 10 K
Ni 500 acc. to DIN43760 - 60 ... +150 C 10 K
Ni 1000 acc. to DIN43760 - 60 ... +150 C 10 K

Thermocouples:

Type B PtRh30-PtRh6 0 ... +1820 C 500 K
Type C W5Rh-W26Re (ASTME 988) 0 ... 2320 C 500 K
Type D W3Rh-W25Re (ASTME 988) 0 ... 2495 C 500 K
Type E NiCr-CuNi -200 ... +915 C 50 K
Type J Fe-CuNi -200 ... +1200 C 50 K
Type K NiCr-Ni -200 ... +1372 C 50 K
Type L Fe-CuNi -200 ... +900 C 50 K
Type N NiCrSi-NiSi -270 ... +1300 C 50 K
Type R Pt13Rh-Pt -50 ... +1768 C 500 K
Type S Pt10Rh-Pt -50 ... +1768 C 500 K
Type T Cu-CuNi (nach IEC 584) -200 ... +400 C 50 K
Type U Cu-CuNi (nach DIN 43710) -200 ... +600 C 50 K
MoRe5-MoRe41 0 ... +2000 C 500 K
Resistance-type sensor: 10 ... 400 Ohm 10 Ohm
10 ... 2000 Ohm 10 Ohm
Voltage sensor: -10 ... 100 mV 5 mV

 

Resistance thermometer:

Sensor connection:     2-, 3- or 4-wire

Meas. current:
    < 0.6 mA

max. perm. line resistance: 11 Ohm / Leitung

Accuracy:    Pt100, Ni100:    +0.2 C or +0.08 % of meas. span
                     Pt500, Ni500:    +0.4 C or +0.16 % of meas. span
                     Pt1000, Ni1000: + 0.2 C or 0.08 % or meas. span

Temperatur effect: Td = + (15 ppm/K* max. meas. range + 50 ppm/K * meas. span)          

Thermocouples:

Sensor connection: 2-wire connection

Sensor current: < 350 nA

Accuracy (typ):     + 0.5 K (Type: K, J, E, L, U),
                               + 1.0 K (Type: N, C, D)
                               +2.0 K (Type: S, B, R, MoRe5-MoRe41)

CJC:    Pt100 internal or external (0 ... 80 C)

CJC accuracy: +1 C

Temperatur effect: Td = +(50ppm/K * max. meas. range + 50 ppm / * meas. span)

Output signal: 4 ... 20 mA or 20 ... 4 mA, 2-wire-technology

Linearisation: temperature linear, resistance linear or voltage linear

Auxiliary energy VS: 8 ... 30 V DC (max. ripple factor: 5 Vss bei VS > 13 V)

Electr. isolation (E/O):    = 3.75 KV AC

Permissible load RA: RA < (VS - 8V) / 0,022 A (RA in Ohm, VS in V)

Digital filter: 0 to 60 s, configurable

Switch-on delay: approx. 4s

Response time: 0.5 s

Output limits: 3.8 ... 20.5 mA

Signal in case of sensor damage: 3,6 mA or > 21,0 mA, configurable

EMC:
        Inerference immunity and emission acc. to EN 61326-1 and NAMUR NE21

Ex-approved: ATEX II 1G EEx ia IIC T4/ T5 / T6

Nominal temperature: 25 C

Operating temperature: -40 ... +85 C

Climate class: acc. to EN 60654-1, class.C; condensation permissible

Vibration strength: 4 g / 2 ... 150 Hz acc. to IEC 60 068-2-6

Electric connection: via terminals, cross section of connection terminals  max. 1.75 mm

Housing: PC-housing, suitable for installation in connection head acc. to DIN 43729 form B

IP-rating: Housing IP 54, connection terminals: IP00

Weight: approx. 40 g

Dimensions: diameter 44 mm x 21 mm



Programmable, electrically isolated universal transmitter GITT 01, basic price

Please order following accessories separately:



= data sheet as *.pdf

= instruction manual as *.pdf

deutsche Beschreibung

Price of the basic article, German V.A.T. incl : EUR 137.30


The net price of the basic article  GITT 01 is:  EUR 115.38 




News