GSMU 1020 C5 - Details

Home --> Devices for Switch Panels / Industry --> Measuring Transducer --> Flow Measuring Transducer



Flow measuring transducer


Properties:

- 3 measuring ranges integrated in each device

- selection between 2 different response times

- High accuracy

- almost independent of flow direction

- shock resistant

- resistant to pollution

Typical application

GSMU 0102: e.g. monitoring of clean rooms and laminar flow GSMU 1020: e.g. air conditioning and ventilation technology,     
                         process and environmental technology

Measuring principle:

No moving parts. 
Hot-film anemometer principle.

 

GSMU 0102 B5

GSMU 0102 C5

GSMU 1020 B5

GSMU 1020 C5

 

Specification 

Measuring range flow: 
       
GSMU 0102:
0 ... 1 m/s, 0 ... 1.5 m/s und 0 ... 2 m/s
        GSMU 1020: 0 ... 10 m/s, 0 ... 15 m/s und 0 ... 20 m/s
        Measuring range can be set by means of jumper

Output signal: 0 - 10 V (out < 1.0 mA) or 4-20 mA (Ri < 450 Ohm)

Measuring accuracy: (at 20 °C, 45 % r.h., 1013 Pa)  
        GSMU 0102: 0 ... 1.0 m/s: + 0.06 m/s + 2 % of measured value
                               0 ... 1,5 m/s: + 0.07 m/s + 3 % of measured value
                                0 ... 2,0 m/s: + 0.07 m/s + 3 % of measured value    
        GSMU 1020: 0 ... 10 m/s: + 0.3 m/s + 3 % of measured value 
                               0 ... 15 m/s: + 0.3 m/s + 3 % of measured value
                                0 ... 20 m/s: + 0.3 m/s + 4 % of measured value
Response time: t90 (at 10 m/s) typ. 2 s or 0.2 s
        The response time can be set by means of jumper

Dependency on flow direction: < 3 % of meas. value at delta alpha < 10 °

Voltage supply: 24 VDC + 10 %, max. 150 mA

Max. load: 500 Ohm


Connection: screw-type terminals 1.5 mm²


Nominal temperature: 20 °C

Operating temperature:
-10 ... + 50 °C


Storage temperature: -20 ... +60 °C


Housing: 80 x 80 x 35 mm (H x W x D)
        Material: ABS
        Protection rating: IP 65


Sensor length: length = 200 (+ 18 mm for sensor head), diameter 12 mm
        GSMU... B5: sensor tube permanently connected to housing
        GSMU... C5: sensor tube connected to housing via cable (approx. 1 m long)
        Other tube or cable lengths upon request.


Electromagnetic compatibility: (EMC):
        CE-conformity acc. to DIN EN 50081-1 and DIN EN 50082-2


 

Accessories (against extra charge)

GNG 24/150: Power supply: 24 V DC, 150 mA


GNT 0520: mains transformer: 230 V to 24 V,
        with mounting clamp and screw-type terminals
        dimensions approx. 62 x 56 x 32.5 mm



Flow measuring transducer for e.g. air conditioning and ventilation technology, process and environmental technology.

  • 3 measuring ranges integrated in 1 device
  • 2 different reply times selectable
  • high accuracy
  • almost independant on flow direction
  • shock resistant
  • resistant against pollution

Please order separately:



= data sheet as *.pdf

deutsche Beschreibung

Price of the basic article, German V.A.T. incl : EUR 306.00


The net price of the basic article  GSMU 1020 C5 is:  EUR 257.14 