Specification:
|
|
|
Sensor element:
|
for Pt 100 acc. to DIN
IEC 751; suitable sensors
available (prepared or unprepared) from stock |
| Sensor
connection: |
2- or 3-wire connection, automatic line resistance
compensation for 3-wire connection. |
|
Meas. range: |
from -200 to
+800 °C
Standard ranges:
GTP 0100: 0 ... 100°C
GTP 0200: 0 ... 200 °C
GTP 5050: -50 ... + 50 °C
GTP 5015: -50 ... +150 °C
OPTION: any
measuring range available against extra charge
|
|
Output
signal: |
4 - 20 mA
(2-wire)
optionally 0 - 1 V, 0 - 2 V, 0 - 5 V,
0 - 10 V (3- or 4-wire)
other output signals upon request |
|
Auxiliary energy: |
Uv = 12 ...
30 V DC (at 0 - 10 V: Uv = 18 ... 30 V DC)
|
| reverse voltage protection: |
50 V
permanently |
| Permissible impedance: |
RA
(Ohm) = Uv (V) - 12 / 0,02 A)
|
| Permissible load: |
RL
(Ohm) > 3000 Ohm |
|
Nominal temperature: |
25 °C
|
| Operating temperature electronics: |
0 ... 70 °C |
|
Accuracy electronics: |
+
0,2 % FS |
| Temperature coefficient:: |
0,05 % / °C |
|
Storage temperature: |
-20 ...
+70 °C |
| Relative
Humidity: |
0 ... 80 % r.H., non condensing
Option: encapsulated PC board |
| PC board dimensions:: |
approx.
56,5 x 73 x 20 mm (H x W x D) |
| Option
snap-on housing: |
for top-hat rail (panel mounting),
Width of housing (pitch) 22.5 mm |
|
Mounting: |
4 holes, 3.5 mm
diameter each
Mounting distance: 43.5 x 58 mm (W x
H) |
|
Miscallaneous: |
potentiometer for zero point and scale |
| Electric
connection: |
screw-type terminals with wire
protection and drill holes for testing pin,
wire diameter max. 1.5 mm2
option: screw-type/plug-in
terminal |
| |
|
| Oerder
codes (example): |
GTP0100, 0 ... 100 °C = 4 - 20 mA
GTP, snap-on housing, -50 ... +200 °C = 0 - 10 V, screw-type/plug-in
terminals
|
| Options: |
|
| - AV010: |
option: output signal 0 - 10 V |
| - AV...: |
option: non-standard output signal
(please specify output signal desired) |
| - MB...: |
option: any measuring range (please specify measuring range
desired)
(at option -AV , -MB there is no
extra charge if at least 10 pieces of the same design are ordered)
|
| - LACK: |
encapsulated PC board
(for outdoor application, i.e.
applications where condensation is possible) |
| - SSK: |
screw-type/plug-in terminals |
| |
|
| PC board for measuring transducer cpl. mounted in water-proof surface-type
housing (IP65) GTMU Type 5 |