Digital controller for temperature and process values
TLK 43
Autotuned, microprocessor based digital controller with 2-, 3-point or
PID-control, 3-point motor valve control and adjustable set point gradient (ramp
function), interface optional
Specification:
Meas. input:
universal input for:
- resistance thermometer: Pt100
(3-wire)
- PTC KTY 81-121,
NTC 103AT-2 (2-wire)
- Thermocouples: B, C, E, J, K,
L, N, R, S, T
- Norm. signal: 0 to 20mA, 4 to20mA,
0 to5V, 0 to10V, 1 to5V, 2 to10V
- mV-signal: 0 to50mV, 0 to
60mV, 12 to 60 mV
Meas.
ranges:
Pt100: -200 to 850°C; PTC: -55
to +150°C; NTC: -50 to +110°C
type J: -160 to1000°C
type K: -270 to1370°C
type S: -50 to +1760°C
Resolution:
temperature: 0.1, 1°C or 0.1°F,
1°F
Norm. signals: scale freely
adjustable, -19999..9999 digit DP selectable
Accuracy :
temperature: +/- 0.15 % FS +/- 1
digit
Meas.
ranges:
8 measurements/sec.
Display:
two lines, each 4-digit, 7 mm high LED
Outputs:
Please pick the possible combinations from the "output
options"-table below.
1(standard) up to max. 4
outputs
available output versions
(Standard=Relay)
- Relay-output (close contact,
switching power: 5A/2A, 250V AC)
- Solid state relay:
14V DC/ 7mA
- Norm. signal 0(4)..20mA
- Norm. signal 0(2)..10Volt
Controller
state:
2-point, 3-point, continuous or
neutral zone or PID control (single or double action), 3-point motor
valve control
Autotuning:
the AUTOTUNING function
guarantees the most briefly programming of all values requested.
Alarm
outputs:
max. 3 (depending on output
configuration)
Analog
output:
scaleable (Norm. signal output
necessary)
Interface (option):
RS 485, optoisolated
Power
supply for transmitter:
12V DC/20mA
Control
inputs:
2 digital inputs that permit
the remote commutation of the set point.
Heater
break function:
(option) :
the controller is available with a current transformer input
for monitoring the heater break.
Housing:
48x48x107mm, panel cutout: 45.5x45.5mm
Mounting by means of clamping
frame
Protection
class:
front IP54 (mounted in panel
with gasket)
Electric
connection:
screw-type terminals
Operating
conditions:
0 to +55°C, 30 to 95% rel.H. (non
condensing)
Storage
temperature:
-10 to +60°C
Power
supply:
standard: 90 to 240V AC +/- 10%,
50/60HZ
option: 24V AC +/-10%
50/60Hz and 24V DC +/- 10%
Power
consumption:
approx. 10VA
For each output wished the referring
option has to be given:
Implementations, Options:
24V:
power supply 18 to 30V AC/DC
HBA:
current transformer input for heater break function
RS485
serial interface and digital control inputs
REL:
Relay output
HLR :
SSR drive
NS-V:
Norm. signal 0(2) to10V
NS-A:
Norm. signal 0(4) to 20mA
Digital controller for temperature and process values, basic price
Autotuned, microprocessor based digital controller with 2-, 3-point or PID-control, 3-point motor valve control and adjustable set point gradient (ramp function), interface optional
= data sheet as *.pdf
= instruction manual as *.pdf
deutsche Beschreibung
Price of the basic article, German V.A.T. incl
:
EUR
219.00
The net price of the basic article TLK43
is:
EUR
184.03
power supply: 90..240VAC (standard)
power supply: 18..30VAC
power supply: 18..30VDC